Electronic 24V Fire Alarm Hooter in Mumbai

Two red electronic fire alarm hooters with slotted grilles, fixed to a concrete wall

Cease Fire & Electrical Services LLP supplies, installs and maintains the 24V fire alarm hooter for buildings in Mumbai, including offices, housing societies, schools, hospitals, factories and warehouses. An electronic 24V hooter is the sounder that gives the evacuation tone when the fire alarm panel detects a fire, running on the panel's 24 V DC supply and battery backup. We supply conventional and addressable hooters to suit your panel and test each one before handover.

How it works

The fire alarm panel powers its sounder circuits from a 24 V DC supply with a standby battery, so hooters keep working during a power cut. When a detector or call point operates, the panel switches on the sounder circuit and every hooter on it gives a continuous tone. Conventional hooters are wired on sounder circuits from the panel; addressable hooters sit on the detector loop and can be switched floor by floor.

Where people may not hear a tone, such as noisy plant rooms, a strobe hooter with a flashing light is the better choice.

Sound levels to plan for

Tone frequency
500 Hz to 1,000 Hz, continuous
Minimum sound level anywhere people may be
65 dB(A), or 5 dB(A) above background noise lasting over 30 seconds, whichever is higher
Sleeping areas
75 dB(A) at the bed head with doors shut
Number of sounders
At least one for each fire compartment
Upper limit
Above 120 dB(A) can damage hearing

A closed door can cut the tone by more than 20 dB, so rooms behind doors often need their own hooter. The same tone should be used throughout a building so everyone recognises it.

What to tell us

System
Conventional or addressable, with the panel make and model
Quantity
Number of hooters and floors
Areas
Office, residential, sleeping, noisy or outdoor areas
Existing tone
The tone already used in the building, if you are adding hooters

Supply, installation and servicing

We supply hooters, fix and wire them to the approved layout, and test each sounder circuit before handover, including a walk-round check that the tone can be heard in every area. Under our AMC, hooters are tested during quarterly visits and the annual service, and the panel batteries that power them are checked.

The panel battery that powers the hooters can be watched continuously through FireSense IoT monitoring, which supports the ACMS now required for covered buildings in Maharashtra.

Engineer on a step ladder fitting a red fire alarm sounder to a corridor wall, a second sounder already fitted further along

Why choose Cease Fire

  • Since 1992

    A Maharashtra Fire Services Licensed Agency (MFS/LA/RF-93/RD-95) that designs, installs and maintains fire alarm systems.

  • Proven on fire alarm work

    Addressable fire alarm systems at 65 Adani Electricity substations in Mumbai.

  • Right part first time

    We confirm panel compatibility and sounder circuit capacity before you order.

Request a quote

Tell us the number of hooters, the floors and areas they will cover, and your panel make and model. We will confirm the right hooter and send a quote.

Frequently asked questions

What is a 24V fire alarm hooter?

It is an electronic sounder that gives the fire alarm tone, powered by the panel's 24 V DC supply. The panel's standby battery keeps it working during a power cut.

How loud should a fire alarm hooter be?

IS 2189 asks for at least 65 dB(A), or 5 dB(A) above lasting background noise, wherever people may be. Sleeping areas need 75 dB(A) at the bed head with doors shut.

How many fire alarm hooters do I need?

At least one in each fire compartment, and enough that the tone reaches the required level in every occupied area. Rooms behind closed doors often need their own hooter, so we work it out from your layout.

What is the difference between a hooter and a strobe hooter?

A hooter gives a tone only. A strobe hooter adds a flashing light for noisy areas and for people who cannot hear the alarm.

Why is my fire alarm hooter not working?

Common causes are a fault on the sounder circuit, a disconnected or damaged hooter, a flat panel battery or a sounder circuit left silenced after a test. The panel usually shows a fault, and our team can trace and fix it.

Can I replace a hooter with a different make?

On a conventional system it usually works if the voltage and current suit the panel's sounder circuit. On an addressable loop the hooter must match the panel's make and protocol, so share the panel model first.

Will a hooter fault show on the fire alarm panel?

Yes. The panel normally shows a fault on a sounder circuit, and FireSense IoT monitoring can report panel and battery faults to the owner and to us as well.

Question not answered here? Call our team, Monday to Saturday, 9 am to 7 pm.

Call +91 9920676281