Cease Fire & Electrical Services LLP supplies components for gas and agent fire suppression systems in Mumbai: Flametrace linear pneumatic fire detection tube and auto-reset pressure switches. These parts are used in tube suppression systems, electrical panel protection and kitchen and clean agent kits. We also design, supply, install and maintain the complete suppression systems they belong to.

Components we supply

  1. Fire detection tube (linear pneumatic)

    Detects heat along its whole length and releases the system by rupturing

    4 mm ID × 6 mm OD, 100 m roll, 41 bar working pressure, activation approx. 115 °C to 140 °C

  2. Pressure switch, auto-reset (SPDT)

    Signals a control or alarm panel when pressure changes

    Operates at 10 ±1 bar and 18 ±1 bar, 240 VAC, R1/8 connection

Fire detection tube

The tube is a non-electrical heat detector. It is kept under pressure, and when flame or heat reaches any point along its length, it ruptures there. The pressure drop opens the valve of the connected cylinder, which discharges the extinguishing agent at the source of the fire.

  • Material: special inert, non-conductive polymer, self-extinguishing, to UL94 V2, halogen-free.
  • Standards: BS ISO 7628 and BS 5409, CE.
  • Working temperature: -40 °C to +110 °C. Bend radius 42 mm.
  • UV and ozone resistant, red in colour, and compatible with inert, low-pressure and high-pressure agents.

Pressure switch

The auto-reset pressure switch changes state between about 10 bar and 18 bar and returns by itself. It is used to signal a control panel or fire alarm panel when the detection tube ruptures or a cylinder discharges.

  • Contacts: SPDT, rated 240 VAC. Minimum cycle life 20,000.
  • Pressure: proof 35 bar, burst 45 bar.
  • Ambient temperature: -30 °C to +70 °C.

Where these components are used

See tube suppression, electrical panel protection, kitchen wet chemical, Novec 1230 and FM-200 systems.

  • Tube suppression systems: for enclosed equipment such as cabinets, machine housings and panels.
  • Electrical panel protection: automatic discharge inside the panel, with a signal to the alarm panel.
  • Kitchen and clean agent systems: detection and release kits using agents such as FK-5-1-12 and FM-200, to NFPA 2001.

Choosing the right component

Share your system details and we will confirm the parts.

  • The agent and cylinder valve the tube must connect to.
  • The length of tube needed for the enclosure, and the bend radius at its route.
  • Whether you need an alarm or shutdown signal from a pressure switch.
  • The electrical rating and connection size on the panel side.

Why choose Cease Fire

  • Since 1992

    1,500+ fire protection projects and the Rashtriya Nirman Ratna Award for Best Government Contractor (2002).

  • Licensed

    Maharashtra Fire Services Licensed Agency (MFS/LA/RF-93/RD-95). See our certifications.

  • System knowledge

    We design and install suppression systems, so we match each component to the system it serves.

  • Documents on request

    Product datasheets can be shared with your quote.

Request a quote

Share the component, quantity and the system it is for. We will confirm the specification and send a quote.

Frequently asked questions

What is a fire detection tube?

It is a pressurised polymer tube that works as a linear heat detector. When heat reaches a point along its length, the tube ruptures, the pressure drops and the connected system is released. It needs no electricity to detect.

How does a detection tube trigger a suppression system?

The tube is connected to the cylinder valve and kept under pressure. When it ruptures at the hot spot, the pressure falls and the valve opens to discharge the agent. It can also trigger a pressure switch to signal an alarm panel.

At what temperature does the detection tube activate?

Our detection tube activates at approximately 115 °C to 140 °C. The exact time depends on the internal pressure, flame intensity and how fast the temperature rises.

What size is the detection tube?

It is 4 mm inside diameter and 6 mm outside diameter, supplied in a 100 m roll. The working pressure is 41 bar.

What does a pressure switch do in a suppression system?

It senses a change in pressure and changes its contacts to signal a control or alarm panel. For example, it can show that the tube has ruptured or the system has discharged.

What are the pressure switch ratings?

Our auto-reset SPDT pressure switch operates at 10 ±1 bar and 18 ±1 bar, has a 240 VAC rating, an R1/8 connection and works in ambient temperatures from -30 °C to +70 °C. Please confirm the details on the datasheet for the exact model.

Which systems use these components?

They are used in tube suppression systems for enclosed equipment, in electrical panel protection and in kitchen and clean agent kits. Ask us which parts suit your system.

Are these used for water sprinkler systems?

No. These are for gas and agent suppression systems. Water sprinkler parts are on the sprinklers page.

How do I get a quote?

Send your requirement to sales@ceasefireservices.com, call +91 9920676281 or use the enquiry form with the part, quantity and location.

Question not answered here? Call our team, Monday to Saturday, 9 am to 7 pm.

Call +91 9920676281