Fire Detection Tube (Linear Pneumatic) in Mumbai

Cease Fire & Electrical Services LLP supplies Flametrace® fire detection tube in Mumbai. It is a pressurised polymer tube that detects heat along its whole length and, when it ruptures, releases a connected fire suppression system. We use it in tube suppression systems for enclosed equipment, in electrical panel protection and in clean agent kits, and we supply it by the metre or roll.
How it works
The tube is kept under pressure and routed through or around the equipment you want to protect. When flame or radiant heat reaches any point on it, the tube softens and ruptures at that spot. The pressure falls, the valve on the connected cylinder opens and the agent is released at the source of the fire. The same drop in pressure can operate a pressure switch to signal an alarm panel. See pressure switch.
Specification
- Product
- Flametrace® fire detection tube, part number 7000101
- Size
- 4 mm inside diameter × 6 mm outside diameter
- Supply
- 100 m roll
- Material
- Inert, non-conductive modified polymer, red, self-extinguishing (UL 94 V2 grade), halogen-free
- Activation temperature
- Approx. 115 °C to 140 °C (depends on pressure, flame intensity and rate of temperature rise)
- Rating
- 172 °C at 15 bar
- Working pressure
- 41 bar
- Working temperature
- -40 °C to +110 °C
- Bend radius
- 42 mm
- Safety ratio
- 1:3
- Standards
- BS ISO 7628:2010, BS 5409, CE
Features
- No electricity: a non-electrical detector and activation device in one.
- Heat detection along its whole length, so a small fire anywhere along the tube sets it off.
- Formulated to resist permeation of the pressurising gas, to hold pressure over time.
- Resists UV, ozone, moisture and most common chemicals, and is heat and light stabilised.
- Compatible with inert, low-pressure and high-pressure agents.
Where it is used
- Tube suppression systems for enclosed equipment such as cabinets, machine housings and compartments. See tube suppression.
- Electrical panel protection, with the tube running inside the panel. See electrical panel protection.
- Kitchen and clean agent kits, for example with FK-5-1-12 and FM-200 systems designed to NFPA 2001. See Novec 1230 and FM-200.
Installation notes
Our engineers do the routing, fitting and testing as part of a complete suppression system.
- Route the tube through the hottest and highest-risk points of the enclosure, and keep every bend at or above the 42 mm radius so it does not kink.
- Clamp it so it cannot rub or be crushed by doors and moving parts.
- Fit it to the correct valve and gauge, then pressurise and leak-test it.
- Keep records of the pressure at commissioning and at every service.

Choosing the right tube setup
We confirm the following before supply:
- The agent and cylinder valve the tube will connect to.
- The length needed, based on the enclosure size and route.
- Whether a pressure switch is needed to signal an alarm or shutdown.
- The ambient temperature at the equipment, against the tube's working range.
Why choose Cease Fire
Since 1992
1,500+ fire protection projects and the Rashtriya Nirman Ratna Award for Best Government Contractor (2002).
Licensed
Maharashtra Fire Services Licensed Agency (MFS/
LA/ ). See our certifications.RF-93/ RD-95 System knowledge
We design and install suppression systems, so we match each part to the system it serves.
Request a quote
Tell us the equipment, the agent and the length you need. We will confirm the parts and send a quote.
Frequently asked questions
What is a fire detection tube?
It is a pressurised polymer tube that works as a linear heat detector. When heat reaches any point along it, the tube ruptures, the pressure drops and the connected suppression system is released.
Does the tube need electricity?
No. It is a non-electrical detection device, so it keeps working in places where electrical detection is difficult or unwelcome, such as inside enclosed equipment.
At what temperature does it activate?
It activates at approximately 115 °C to 140 °C. The exact time depends on the internal pressure, the flame intensity and how fast the temperature rises.
How long is the tube and what size?
It comes in a 100 m roll and measures 4 mm inside diameter by 6 mm outside diameter. We cut it to the length your enclosure needs.
Can it be fitted next to galvanised metal?
Yes. The material is formulated to avoid surface damage when installed on galvanised metal and equipment.
Which suppression systems use this tube?
It works with inert, low-pressure and high-pressure agents, so it is used in tube suppression systems, electrical panel protection and clean agent kits. Ask us which cylinder valve and agent suit your equipment.
What happens after the tube ruptures?
The system discharges, and the tube and cylinder must be restored by a trained technician before the equipment is protected again. Our AMC covers inspection, recharging and replacement.
Question not answered here? Call our team, Monday to Saturday, 9 am to 7 pm.
Call +91 9920676281