Cease Fire & Electrical Services LLP designs, installs and maintains the FM-200 fire suppression system for server rooms, data centres, control rooms, archives and UPS rooms in Mumbai. An FM-200 fire suppression system floods a closed room with the clean agent HFC-227ea, which absorbs heat and puts out the fire in about 10 seconds without water or residue. We size every system with a room-by-room design sheet and maintain it under AMC as a Maharashtra Fire Services Licensed Agency.

How an FM-200 system works

Smoke detectors in two zones sense a fire and signal the releasing panel. The panel sounds hooters and strobes, counts down so people can leave, and then opens the FM-200 cylinder. The agent flows through pipework to nozzles in the room, ceiling void and floor void. It absorbs heat from the fire and puts it out quickly, and it leaves nothing to clean up.

A sample design sheet

Every FM-200 system we quote comes with a design sheet. Here is one of ours for a small server room:

Room size
3.64 m × 1.61 m × 3.03 m (about 17.8 m³), no ceiling or floor void
Hazard class
Class A and C (ordinary combustibles and electrical equipment)
Design concentration
7% by volume
Design temperature
21 °C
Agent needed
About 10 kg, from the NFPA 2001 calculation
Cylinder and nozzles
One 22-litre cylinder, one discharge nozzle
Detection and control
Two detection zones, releasing panel, manual release and abort units, hooter and response indicator

Your design sheet will show the same items for each of your rooms, so you can see exactly what you are paying for.

Where FM-200 systems are used

  • Engineer checking a floor-level detector in a data centre aisle between server cabinets

    Server rooms, data centres and telecom rooms

  • Engineer checking a red fire extinguisher on the wall of a control room with an operator desk, monitors and a mimic panel

    Control rooms, UPS rooms and battery rooms

  • Engineer with a tablet looking up at a ceiling nozzle in an archive aisle between shelves of box files

    Archives, record rooms and libraries

  • Engineer checking a fire blanket and extinguisher on the wall of a laboratory with benches, glassware and a fume cupboard

    Hospital equipment rooms and laboratories

  • Engineer comparing a drawing against a line of switchboard panels in an electrical room

    Electrical rooms that are occupied from time to time

Components

  • Two red gas suppression cylinders strapped to a wall, with valves, gauges and discharge hoses to a manifold

    FM-200 cylinder with valve

    Stores the agent as a liquid under nitrogen pressure, filled to 25 bar

  • A cylinder valve fitted with a black solenoid actuator and a red lever actuator with a safety pin

    Solenoid and manual actuators

    Open the cylinder valve automatically or by hand

  • Red fire pipework on a wall: a riser meeting a main at a tee, with grooved couplings and clamps

    Discharge hose, pipework and nozzles

    Spread the agent through the room and voids

  • Three white round smoke detectors fixed in a row to a concrete ceiling

    Smoke detectors in two zones

    Confirm the fire before release, to avoid false discharge

  • A red gas release control panel with a small display, indicator lamps and a key switch

    Releasing control panel

    Sounds the warning, counts down and releases the agent

  • A yellow manual release unit beside a blue abort switch, on a concrete wall

    Manual release and abort units

    Let staff release the system or hold the release

  • Two red fire alarm sounders with clear strobe lenses, fixed to a concrete wall

    Hooters, strobes, response indicator and warning signs

    Warn people to leave and show the system has operated

Safety and the environment

Occupied rooms: FM-200's no-observed-adverse-effect level (NOAEL) is 9%, above the 7% design concentration commonly used for Class A and C hazards, so it is used in rooms where people work. People should still leave when the alarm sounds.

HFC phase-down: HFC-227ea is a hydrofluorocarbon. Under the Kigali Amendment, India will cut HFC use in steps from 2032 (10% by 2032, 20% by 2037, 30% by 2042 and 85% by 2047). Existing systems can be kept and serviced, and for new rooms we also explain FK-5-1-12 and inert gas options.

Design standards

We design FM-200 systems to NFPA 2001, the standard for clean agent fire extinguishing systems, and to UL/FM requirements where the project calls for them. NFPA 2001 asks for halocarbon agents to discharge in about 10 seconds and for the room to hold the agent for at least 10 minutes, so we check openings and can arrange a door fan test of the room's tightness.

Our process

  1. Free site survey

    We measure the rooms and voids, and check openings, ventilation and any existing system.

  2. Design

    A design sheet for each room, cylinder and nozzle layout, and the detection and release sequence.

  3. Supply and installation

    Cylinders, pipework, nozzles, detectors and the releasing panel, installed by our own team.

  4. Testing and commissioning

    Detection and release circuits tested, room openings sealed, and staff trained on the warning and abort sequence.

  5. Form A

    As a licensed agency, we issue Form A for the work, which you submit to the fire brigade.

  6. AMC and Form B

    Agent quantity and pressure checked at least every six months, and Form B every January and July.

Our experience

  • Licences

    Maharashtra Fire Services Licensed Agency (MFS/LA/RF-93/RD-95) and Maharashtra Electrical Contractor Licence No. 17545.

  • Electrical and utility work

    Addressable fire alarm systems at 65 Adani Electricity receiving substations across Mumbai, May 2024 to January 2026.

  • Clients

    Including TCS, BPCL, Godrej and Adani Electricity Mumbai.

See all projects and case studies

Maintenance and Form B

Under AMC we weigh or check the pressure of every FM-200 cylinder at least every six months, test the detectors, panel, actuators and warning devices each year, and tell you when changes to the room affect the design. A licensed agency must inspect the fire systems and issue Form B every January and July, and we can include this in your AMC.

Why choose Cease Fire

  • Since 1992

    1,500+ projects and the Rashtriya Nirman Ratna Award for Best Government Contractor (2002).

  • Clear design sheets

    Every room calculated and shown to you before you order.

  • Honest agent advice

    FM-200, FK-5-1-12, inert gas or CO2, whichever suits the room.

  • Licensed

    We issue Form A and Form B ourselves.

Book a free site survey

Send us the room sizes, including any false ceiling and raised floor, or book a visit. We will send a proposal with a design sheet for each room.

Frequently asked questions

What is an FM-200 fire suppression system?

It is a clean agent system that floods a closed room with HFC-227ea gas. The agent absorbs heat and puts out the fire in seconds, without water or residue.

Is FM-200 safe for people?

At normal design concentrations, yes. Its no-observed-adverse-effect level is 9%, above the usual 7% design concentration, but people should still leave the room when the alarm sounds.

How much FM-200 does a room need?

It depends on the room and void volumes, hazard class, design concentration and temperature. For example, a 17.8 m³ server room at 7% and 21 °C needs about 10 kg.

Is FM-200 being phased out in India?

HFC-227ea is an HFC covered by the Kigali Amendment. India will reduce HFC use in steps from 2032, so existing systems can be kept and serviced, while new projects may also consider FK-5-1-12 or inert gas.

What is the difference between FM-200 and Novec 1230?

Both are clean agents that suit occupied rooms and leave no residue. FK-5-1-12 (Novec 1230) has a much lower global warming potential, while FM-200 has been used widely for longer.

Can an existing FM-200 system be refilled?

Yes, after a discharge the cylinder is refilled and the system recommissioned. We check the system's condition and the room before it is put back in service.

How often should an FM-200 system be serviced?

Agent quantity and pressure should be checked at least every six months, with a full inspection each year. A licensed agency must also inspect the fire systems for Form B every January and July.

Are UL listed and FM approved FM-200 systems available?

Yes. Where your consultant or insurer asks for UL listed or FM approved components, we can supply them. Tell us the requirement at the survey.