FM-200 Fire Suppression System in Mumbai
Cease Fire & Electrical Services LLP designs, installs and maintains the FM-200 fire suppression system for server rooms, data centres, control rooms, archives and UPS rooms in Mumbai. An FM-200 fire suppression system floods a closed room with the clean agent HFC-227ea, which absorbs heat and puts out the fire in about 10 seconds without water or residue. We size every system with a room-by-room design sheet and maintain it under AMC as a Maharashtra Fire Services Licensed Agency.
How an FM-200 system works
Smoke detectors in two zones sense a fire and signal the releasing panel. The panel sounds hooters and strobes, counts down so people can leave, and then opens the FM-200 cylinder. The agent flows through pipework to nozzles in the room, ceiling void and floor void. It absorbs heat from the fire and puts it out quickly, and it leaves nothing to clean up.
A sample design sheet
Every FM-200 system we quote comes with a design sheet. Here is one of ours for a small server room:
- Room size
- 3.64 m × 1.61 m × 3.03 m (about 17.8 m³), no ceiling or floor void
- Hazard class
- Class A and C (ordinary combustibles and electrical equipment)
- Design concentration
- 7% by volume
- Design temperature
- 21 °C
- Agent needed
- About 10 kg, from the NFPA 2001 calculation
- Cylinder and nozzles
- One 22-litre cylinder, one discharge nozzle
- Detection and control
- Two detection zones, releasing panel, manual release and abort units, hooter and response indicator
Your design sheet will show the same items for each of your rooms, so you can see exactly what you are paying for.
Where FM-200 systems are used

Server rooms, data centres and telecom rooms

Control rooms, UPS rooms and battery rooms

Archives, record rooms and libraries

Hospital equipment rooms and laboratories

Electrical rooms that are occupied from time to time
Components

FM-200 cylinder with valve
Stores the agent as a liquid under nitrogen pressure, filled to 25 bar

Solenoid and manual actuators
Open the cylinder valve automatically or by hand

Discharge hose, pipework and nozzles
Spread the agent through the room and voids

Smoke detectors in two zones
Confirm the fire before release, to avoid false discharge

Releasing control panel
Sounds the warning, counts down and releases the agent

Manual release and abort units
Let staff release the system or hold the release

Hooters, strobes, response indicator and warning signs
Warn people to leave and show the system has operated
Safety and the environment
Occupied rooms: FM-200's no-observed-adverse-effect level (NOAEL) is 9%, above the 7% design concentration commonly used for Class A and C hazards, so it is used in rooms where people work. People should still leave when the alarm sounds.
HFC phase-down: HFC-227ea is a hydrofluorocarbon. Under the Kigali Amendment, India will cut HFC use in steps from 2032 (10% by 2032, 20% by 2037, 30% by 2042 and 85% by 2047). Existing systems can be kept and serviced, and for new rooms we also explain FK-5-1-12 and inert gas options.
Design standards
We design FM-200 systems to NFPA 2001, the standard for clean agent fire extinguishing systems, and to UL/FM requirements where the project calls for them. NFPA 2001 asks for halocarbon agents to discharge in about 10 seconds and for the room to hold the agent for at least 10 minutes, so we check openings and can arrange a door fan test of the room's tightness.
Our process
Free site survey
We measure the rooms and voids, and check openings, ventilation and any existing system.
Design
A design sheet for each room, cylinder and nozzle layout, and the detection and release sequence.
Supply and installation
Cylinders, pipework, nozzles, detectors and the releasing panel, installed by our own team.
Testing and commissioning
Detection and release circuits tested, room openings sealed, and staff trained on the warning and abort sequence.
Form A
As a licensed agency, we issue Form A for the work, which you submit to the fire brigade.
AMC and Form B
Agent quantity and pressure checked at least every six months, and Form B every January and July.
Our experience
Licences
Maharashtra Fire Services Licensed Agency (MFS/LA/RF-93/RD-95) and Maharashtra Electrical Contractor Licence No. 17545.
Electrical and utility work
Addressable fire alarm systems at 65 Adani Electricity receiving substations across Mumbai, May 2024 to January 2026.
Clients
Including TCS, BPCL, Godrej and Adani Electricity Mumbai.
Maintenance and Form B
Under AMC we weigh or check the pressure of every FM-200 cylinder at least every six months, test the detectors, panel, actuators and warning devices each year, and tell you when changes to the room affect the design. A licensed agency must inspect the fire systems and issue Form B every January and July, and we can include this in your AMC.
Why choose Cease Fire
Since 1992
1,500+ projects and the Rashtriya Nirman Ratna Award for Best Government Contractor (2002).
Clear design sheets
Every room calculated and shown to you before you order.
Honest agent advice
FM-200, FK-5-1-12, inert gas or CO2, whichever suits the room.
Licensed
We issue Form A and Form B ourselves.
Book a free site survey
Send us the room sizes, including any false ceiling and raised floor, or book a visit. We will send a proposal with a design sheet for each room.
Frequently asked questions
What is an FM-200 fire suppression system?
It is a clean agent system that floods a closed room with HFC-227ea gas. The agent absorbs heat and puts out the fire in seconds, without water or residue.
Is FM-200 safe for people?
At normal design concentrations, yes. Its no-observed-adverse-effect level is 9%, above the usual 7% design concentration, but people should still leave the room when the alarm sounds.
How much FM-200 does a room need?
It depends on the room and void volumes, hazard class, design concentration and temperature. For example, a 17.8 m³ server room at 7% and 21 °C needs about 10 kg.
Is FM-200 being phased out in India?
HFC-227ea is an HFC covered by the Kigali Amendment. India will reduce HFC use in steps from 2032, so existing systems can be kept and serviced, while new projects may also consider FK-5-1-12 or inert gas.
What is the difference between FM-200 and Novec 1230?
Both are clean agents that suit occupied rooms and leave no residue. FK-5-1-12 (Novec 1230) has a much lower global warming potential, while FM-200 has been used widely for longer.
Can an existing FM-200 system be refilled?
Yes, after a discharge the cylinder is refilled and the system recommissioned. We check the system's condition and the room before it is put back in service.
How often should an FM-200 system be serviced?
Agent quantity and pressure should be checked at least every six months, with a full inspection each year. A licensed agency must also inspect the fire systems for Form B every January and July.
Are UL listed and FM approved FM-200 systems available?
Yes. Where your consultant or insurer asks for UL listed or FM approved components, we can supply them. Tell us the requirement at the survey.
Question not answered here? Call our team, Monday to Saturday, 9 am to 7 pm.