Break Glass Manual Call Point in Mumbai

Two red break-glass manual call points on a concrete wall, a small hammer on a chain beside one

Cease Fire & Electrical Services LLP supplies, installs and maintains the break glass manual call point for fire alarm systems in Mumbai, for offices, housing societies, hospitals, hotels, schools, factories and warehouses. A manual call point (MCP) lets anyone who sees a fire raise the alarm by breaking its glass, and the alarm stays on at the panel until the call point is reset. We supply conventional and addressable call points to suit your panel and fix them near exits and staircases where people will look for them.

How a break glass call point works

Breaking the glass releases a switch inside the call point, which signals the fire alarm panel. The alarm sounds on the floor and at the panel, and the panel keeps the alarm on even if someone presses the call point again. After a fire or a test, the glass is replaced and the call point is reset.

Call points for fire alarms are red, and each one should match the rest in the building so people recognise it at once.

Where manual call points are fixed

IS 2189:2008, the Indian code of practice for fire detection and alarm systems, sets these rules:

Maximum travel distance to the nearest call point
30 m inside the building; 45 m where call points are outside
Mounting height
1.4 m above the floor
Preferred position
Near the entry to staircases on each floor
Position
Easy to reach, well lit, clearly visible and free of obstructions
Long corridors
Surface or semi-recessed, so the side is visible
Enclosure
Dust and moisture proof, sealed with a rubber lining
Glass
At least 30 cm² in area and no more than 2 mm thick

Where access is difficult or the risk is high, the travel distance may need to be less than 30 m.

Break glass or push type

  1. How it operates

    Break the glass element

    Press the plastic element firmly

  2. After use

    Replace the glass, then reset

    Reset with a key; nothing to replace

  3. Food preparation areas

    Better avoided, because of broken glass

    Preferred

  4. Recognition

    The traditional type most people know

    Looks similar; works the same way for the user

Both types come in conventional and addressable versions. Replacements must match your panel's make and protocol.

Supply, installation and servicing

We supply call points with their back boxes, fix them at the correct height and position, wire them to the panel and test each one before handover. Under our AMC, call points are operated and checked during quarterly visits and the annual service, and we check that none have been blocked or hidden by later changes to the building.

Call point operation and panel status can also be reported through FireSense IoT monitoring, which supports the ACMS now required for covered buildings in Maharashtra.

Engineer testing a fire alarm call point in a school corridor

Why choose Cease Fire

  • Since 1992

    A Maharashtra Fire Services Licensed Agency (MFS/LA/RF-93/RD-95) that designs, installs and maintains fire alarm systems.

  • Proven on fire alarm work

    Addressable fire alarm systems at 65 Adani Electricity substations in Mumbai.

  • Right part first time

    We confirm panel compatibility before you order replacement call points.

Request a quote

Tell us the number of call points, the number of floors, and your panel make and model if you are adding or replacing call points. We will confirm the right type and send a quote.

Frequently asked questions

What is a break glass manual call point?

It is a red wall-mounted device that lets a person raise the fire alarm by breaking its glass. The panel sounds the alarm and shows which call point or zone was used.

At what height should a manual call point be installed?

IS 2189 says call points should be fixed 1.4 m above the floor, in well-lit, visible positions free of obstructions.

How far apart should manual call points be?

Nobody should have to travel more than 30 m to reach a call point inside the building, or 45 m where call points are outside. Call points are usually placed near staircase entries on each floor.

What happens after the glass is broken?

The alarm sounds on the floor and at the panel, and stays on until it is reset. The glass is then replaced and the call point reset.

Should I choose a break glass or a push type call point?

Break glass is the traditional type most people recognise. Push type call points reset with a key and have no glass to replace, so they suit kitchens and food areas.

Can I replace a call point on my existing fire alarm system?

Yes, if the new call point matches your panel's make and protocol, especially on addressable systems. Share the panel model and we will confirm a compatible replacement.

Can manual call point and panel status be monitored remotely?

Yes. FireSense IoT monitoring reports fire alarm panel, detection and manual call point status to the owner and to us, which supports the ACMS required for covered buildings in Maharashtra.