Break Glass Manual Call Point in Mumbai

Cease Fire & Electrical Services LLP supplies, installs and maintains the break glass manual call point for fire alarm systems in Mumbai, for offices, housing societies, hospitals, hotels, schools, factories and warehouses. A manual call point (MCP) lets anyone who sees a fire raise the alarm by breaking its glass, and the alarm stays on at the panel until the call point is reset. We supply conventional and addressable call points to suit your panel and fix them near exits and staircases where people will look for them.
How a break glass call point works
Breaking the glass releases a switch inside the call point, which signals the fire alarm panel. The alarm sounds on the floor and at the panel, and the panel keeps the alarm on even if someone presses the call point again. After a fire or a test, the glass is replaced and the call point is reset.
Call points for fire alarms are red, and each one should match the rest in the building so people recognise it at once.
Where manual call points are fixed
IS 2189:2008, the Indian code of practice for fire detection and alarm systems, sets these rules:
- Maximum travel distance to the nearest call point
- 30 m inside the building; 45 m where call points are outside
- Mounting height
- 1.4 m above the floor
- Preferred position
- Near the entry to staircases on each floor
- Position
- Easy to reach, well lit, clearly visible and free of obstructions
- Long corridors
- Surface or semi-recessed, so the side is visible
- Enclosure
- Dust and moisture proof, sealed with a rubber lining
- Glass
- At least 30 cm² in area and no more than 2 mm thick
Where access is difficult or the risk is high, the travel distance may need to be less than 30 m.
Break glass or push type
How it operates
Break glassBreak the glass element
Push type (resettable)Press the plastic element firmly
After use
Break glassReplace the glass, then reset
Push type (resettable)Reset with a key; nothing to replace
Food preparation areas
Break glassBetter avoided, because of broken glass
Push type (resettable)Preferred
Recognition
Break glassThe traditional type most people know
Push type (resettable)Looks similar; works the same way for the user
Both types come in conventional and addressable versions. Replacements must match your panel's make and protocol.
Supply, installation and servicing
We supply call points with their back boxes, fix them at the correct height and position, wire them to the panel and test each one before handover. Under our AMC, call points are operated and checked during quarterly visits and the annual service, and we check that none have been blocked or hidden by later changes to the building.
Call point operation and panel status can also be reported through FireSense IoT monitoring, which supports the ACMS now required for covered buildings in Maharashtra.

Why choose Cease Fire
Since 1992
A Maharashtra Fire Services Licensed Agency (MFS/
LA/ ) that designs, installs and maintains fire alarm systems.RF-93/ RD-95 Proven on fire alarm work
Addressable fire alarm systems at 65 Adani Electricity substations in Mumbai.
Right part first time
We confirm panel compatibility before you order replacement call points.
Request a quote
Tell us the number of call points, the number of floors, and your panel make and model if you are adding or replacing call points. We will confirm the right type and send a quote.
Frequently asked questions
What is a break glass manual call point?
It is a red wall-mounted device that lets a person raise the fire alarm by breaking its glass. The panel sounds the alarm and shows which call point or zone was used.
At what height should a manual call point be installed?
IS 2189 says call points should be fixed 1.4 m above the floor, in well-lit, visible positions free of obstructions.
How far apart should manual call points be?
Nobody should have to travel more than 30 m to reach a call point inside the building, or 45 m where call points are outside. Call points are usually placed near staircase entries on each floor.
What happens after the glass is broken?
The alarm sounds on the floor and at the panel, and stays on until it is reset. The glass is then replaced and the call point reset.
Should I choose a break glass or a push type call point?
Break glass is the traditional type most people recognise. Push type call points reset with a key and have no glass to replace, so they suit kitchens and food areas.
Can I replace a call point on my existing fire alarm system?
Yes, if the new call point matches your panel's make and protocol, especially on addressable systems. Share the panel model and we will confirm a compatible replacement.
Can manual call point and panel status be monitored remotely?
Yes. FireSense IoT monitoring reports fire alarm panel, detection and manual call point status to the owner and to us, which supports the ACMS required for covered buildings in Maharashtra.
Question not answered here? Call our team, Monday to Saturday, 9 am to 7 pm.