Emergency Exit Lights and Lighting Signage in Mumbai

A lit green exit sign with a running-figure pictogram above a grey door, and a twin-spot emergency light beside it

Cease Fire & Electrical Services LLP supplies and installs emergency exit lights and emergency lighting signage in Mumbai for residential towers, offices, factories, hospitals and public buildings. An emergency exit light is an LED exit sign with its own battery that stays lit when the mains power fails, so people can find the way out. As a licensed fire agency and electrical contractor, we plan, wire and test the lights ourselves.

What the National Building Code asks for

The National Building Code of India 2016 (Part 4) sets these requirements for exit signs and emergency lighting:

Exit signs
At all exits, emergency exits and escape routes
Backup duration
Emergency lighting must hold the required light level for at least 90 minutes after mains failure
Changeover
Must come on within 5 seconds of the normal lighting failing
Mounting height
Luminaires at least 2 m above floor level
Floor lighting
At least 10 lux on the centre line of escape routes

Your fire authority or consultant may add requirements for your building type. We follow the approved fire drawings.

Types of emergency lighting

  1. Illuminated exit sign

    LED "EXIT" or running-man sign with battery backup

    Exit doors, staircase entries, corridor turns

  2. Directional exit sign

    Exit sign with an arrow showing the escape direction

    Corridors, lobbies, large floors

  3. Emergency escape light

    Battery-backed light that lights the floor of the escape route

    Staircases, corridors, basements

  4. Maintained fitting

    Stays lit all the time and continues on battery when power fails

    Cinemas, malls, hospitals, spaces used at night

  5. Non-maintained fitting

    Lights up only when the power fails

    Offices, factories, residential staircases

For signs that glow without power or wiring, see our emergency exit sign boards.

Where emergency exit lights are needed

  • Staircases, lift lobbies and refuge areas in high-rise residential towers
  • Corridors and exits in offices, malls and hospitals
  • Factory floors, warehouses and basements
  • Schools, auditoriums and hotels

Supply, installation and testing

We review your floor plans or walk the site, mark where each light and sign goes, and supply fittings to suit: single- and double-sided exit signs, maintained and non-maintained fittings, and self-contained or central battery systems. Our electrical team wires them to the correct circuit and tests that each one switches on when power is cut. Batteries lose capacity over time, so we check the lights during AMC visits and replace failed units.

Engineer on a step ladder fitting a lit green exit sign above a corridor door, an emergency light on the wall beside it

Why choose Cease Fire

  • Fire and electrical together

    Licensed fire agency since 1992 (MFS/LA/RF-93/RD-95) and Maharashtra Electrical Contractor (Licence No. 17545).

  • Planned, not just supplied

    Positions follow your escape routes and fire drawings.

  • One team

    Signage, emergency lighting, fire alarm and fire fighting systems.

Request a quote

Share your floor plans, building type and number of floors, or a list of the lights you need. We will prepare a layout and quote.

Frequently asked questions

What is an emergency exit light?

It is an illuminated exit sign with a built-in battery. When the mains power fails, it stays lit so people can see the way out.

How long must emergency lighting last in India?

The National Building Code 2016 asks for emergency lighting that holds the required light level for at least 90 minutes after power fails. It must come on within 5 seconds.

What is the difference between maintained and non-maintained emergency lights?

A maintained light is on all the time and continues on battery during a power cut. A non-maintained light stays off and switches on only when the power fails.

Are emergency exit lights mandatory?

The NBC requires exit signs at all exits and escape routes, and emergency lighting for escape routes. Whether signs must be illuminated depends on the building type and your fire authority's approval.

What is the difference between an exit light and a glow-in-the-dark exit sign?

An exit light uses LEDs and a battery and is brighter. A photoluminescent sign needs no power and glows after absorbing light. Many buildings use both.

At what height should exit lights be installed?

The NBC asks for emergency luminaires at least 2 m above floor level. We fix exit signs above doors and at corridor turns so they are visible along the route.

Do you supply central battery emergency lighting?

Yes. We supply self-contained fittings with their own batteries and central battery systems that feed many fittings from one unit. Our licensed electricians wire, install and test both.

Do you test emergency lights during AMC visits?

Yes. We check that each light and sign switches on when power is cut, and we replace failed batteries or units.