Cease Fire & Electrical Services LLP supplies and installs the pendent sprinkler for offices, flats, hotels, hospitals, shops and schools in Mumbai. A pendent sprinkler hangs down from the branch pipe, usually through a false ceiling, and sprays water in a circle onto the floor below when its glass bulb bursts in the heat of a fire. We match each head's temperature rating, K-factor and response type to the room it protects.

What to specify

K-factor (flow)
K5.6 (K80) for most light and ordinary hazard rooms; K8.0 (K115) where the design needs more flow
Temperature rating
68 °C (red) for most rooms; higher ratings near heat sources
Response
Quick response for light hazard areas such as offices, flats and hotels; standard response where the design calls for it
Fitting
Standard pendent, or recessed with an escutcheon plate for a neater ceiling
Finish
As your specification requires
Approval
UL listed, FM approved, or to IS 9972, as your specification requires

We confirm heads against your design and specification before supply.

Glass bulb colours and temperature ratings

Orange
57 °C
Red
68 °C
Yellow
79 °C
Green
93 °C
Blue
141 °C
Mauve
182 °C
Black
227 °C and 260 °C

These are the glass bulb ratings in IS 9972, the Indian Standard for automatic sprinkler heads. The rating should be about 30 °C above the highest normal temperature in the room.

Where pendent sprinklers are used

  • Offices and shops: below false ceilings in work areas, corridors and lobbies.
  • Flats and hotel rooms: in rooms and passages of high-rise residential towers and hotels.
  • Hospitals and schools: in wards, classrooms and corridors.
  • Below obstructions: under ducts or wide beams, where a head above would be blocked.

Supply, installation and servicing

We supply pendent heads with the right escutcheons and, where needed, flexible sprinkler hoses to set the drop height in false ceilings. On our projects we fit and pressure-test them as part of the sprinkler system. During AMC visits we look for painted, damaged, corroded or blocked heads and replace them with heads of the same type, rating and K-factor.

Engineer on a step ladder adjusting a sprinkler head on red ceiling pipework in a basement car park

Why choose Cease Fire

  • Since 1992

    A Maharashtra Fire Services Licensed Agency (MFS/LA/RF-93/RD-95) with 1,500+ projects.

  • Design experience

    We design and install sprinkler systems to NFPA, NBC and FM guidelines, so each head suits its room.

  • One supplier

    Sprinkler heads, hoses, valves and installation from one team.

Request a sprinkler quote

Send your BOQ or drawings, or the number of heads with K-factor, temperature rating and finish. We will confirm the specification and quote.

Frequently asked questions

What is a pendent sprinkler?

It is a sprinkler head that hangs down from the pipe, usually through a false ceiling. When its bulb bursts, water hits the deflector and sprays in a circle onto the area below.

What is the difference between a pendent and an upright sprinkler?

A pendent sprinkler points down and is used below ceilings. An upright sprinkler points up from exposed pipes and is used where there is no false ceiling. They are not interchangeable, because each deflector is shaped for its own direction.

What does the colour of a sprinkler bulb mean?

It shows the temperature at which the bulb bursts. For example, red is 68 °C, yellow 79 °C and green 93 °C.

What is a quick response sprinkler?

It has a thinner, more sensitive bulb that opens sooner than a standard response head. Quick response heads are used in light hazard areas such as offices, flats and hotels.

Can I paint a sprinkler head to match the ceiling?

No. Paint can delay or stop the head from opening. Painted heads must be replaced, not cleaned.

Can you supply UL listed or FM approved pendent sprinklers?

Yes. UL listed and FM approved sprinklers are available. Tell us what your consultant or insurer specifies, and we will share the manufacturer's certificate for the exact model with our quote.

Can you replace damaged or painted sprinkler heads in an existing building?

Yes. We replace damaged, corroded or painted heads with heads of the same type, rating and K-factor, and check the layout where the room use has changed.