Upright Sprinkler Heads in Mumbai

Cease Fire & Electrical Services LLP supplies and installs the upright sprinkler for car parks, plant rooms, stores, factories and warehouses in Mumbai. An upright sprinkler points up from exposed pipework, and its deflector throws water up towards the ceiling and then down over the area below. It is the usual choice wherever there is no false ceiling and the pipes run in the open.
What to specify
- K-factor (flow)
- K5.6 (K80) for most light and ordinary hazard areas; K8.0 (K115) or larger where the design needs more flow
- Temperature rating
- 68 °C (red) for most areas; 79 °C (yellow) or 93 °C (green) in hot areas such as plant rooms and under roofs
- Response
- Standard or quick response, as the design requires
- Guard
- Wire guard where heads could be knocked, such as in stores and loading areas
- Approval
- UL listed, FM approved, or to IS 9972, as your specification requires
We confirm heads against your design and specification before supply.
Where upright sprinklers are used

Basement and podium car parks
Exposed pipes below the slab.

Plant rooms, pump rooms and service areas
Where pipes run in the open.

Stores, workshops and factories
Under roofs and slabs without false ceilings.

Warehouses
At roof level where storage is not high enough to need ESFR heads.
Upright or pendent?
Direction
Upright sprinklerPoints up from the pipe
Pendent sprinklerHangs down from the pipe
Ceiling
Upright sprinklerExposed pipes, no false ceiling
Pendent sprinklerBelow a false ceiling
Typical areas
Upright sprinklerCar parks, plant rooms, stores, factories
Pendent sprinklerOffices, flats, hotels, hospitals
Interchangeable?
Upright sprinklerNo, the deflectors are shaped differently
Pendent sprinklerNo
Supply, installation and servicing
We supply upright heads, with guards where needed, and fit them as part of the sprinkler system, keeping the deflector the right distance below the slab or roof. During AMC visits we look for heads that are painted, corroded, loaded with dust or blocked by stored goods, and replace them with heads of the same type, rating and K-factor.

Why choose Cease Fire
Since 1992
A Maharashtra Fire Services Licensed Agency (MFS/
LA/ ) with 1,500+ projects.RF-93/ RD-95 Industrial experience
Roof sprinklers with seismic bracing for Roquette India's godowns in Pantnagar, to FM guidelines.
One supplier
Sprinkler heads, valves and installation from one team.
Request a sprinkler quote
Send your BOQ or drawings, or the number of heads with K-factor, temperature rating and guard needs. We will confirm the specification and quote.
Frequently asked questions
What is an upright sprinkler?
It is a sprinkler head that points up from the pipe. Its deflector throws water up towards the ceiling and then down over the area below.
Where are upright sprinklers used?
Where pipes are exposed and there is no false ceiling, such as car parks, plant rooms, stores, factories and warehouses.
Can I fit an upright sprinkler upside down as a pendent?
No. The deflector is shaped for one direction only, and a head fitted the wrong way will not spray correctly.
Why do some upright sprinklers have a guard?
A wire guard protects the head from being knocked and opened by accident. Guards are used in stores, loading areas and anywhere goods or vehicles pass close to the heads.
What temperature rating should an upright sprinkler have?
Most areas use 68 °C heads. Hot areas, such as plant rooms or under a metal roof, may need 79 °C or 93 °C heads.
Can you supply UL listed or FM approved upright sprinklers?
Yes. UL listed and FM approved sprinklers are available. Tell us what your consultant or insurer specifies, and we will share the manufacturer's certificate for the exact model with our quote.
Have you installed upright sprinklers on an industrial project?
Yes. We installed roof sprinklers with seismic bracing for Roquette India's godowns in Pantnagar, to FM guidelines. See the project page.
Question not answered here? Call our team, Monday to Saturday, 9 am to 7 pm.
Call +91 9920676281