ESFR Sprinklers for Warehouses in Mumbai

Cease Fire & Electrical Services LLP supplies and installs the ESFR sprinkler for warehouses, logistics hubs and factory stores with high-piled or rack storage in Mumbai and across Maharashtra. ESFR stands for early suppression, fast response: these large-orifice heads open quickly and discharge heavy drops of water at high flow, to put a storage fire down rather than only hold it back. Installed at roof level, they can often protect racks without in-rack sprinklers, which keeps aisles and racks free of extra pipework.
ESFR K-factors
K14.0
K-factor (metric)K200
NotesPendent and upright models are made
K16.8
K-factor (metric)K240
NotesMostly pendent
K22.4
K-factor (metric)K320
NotesPendent, for taller buildings and higher storage
K25.2
K-factor (metric)K360
NotesPendent, for taller buildings and higher storage
The K-factor, operating pressure and number of heads come from the storage height, roof height and commodity, per the design standard and each head's listing.
When ESFR works, and when it does not
- Works well: open-frame racks and palletised or solid-piled storage under a roof up to the height the head is listed for. NFPA 13 allows ESFR without in-rack sprinklers for open-frame racks in buildings up to 45 ft (13.7 m), for commodities up to cartoned unexpanded Group A plastics.
- Needs care: beams, ducts, lights and cable trays near the heads can block the spray, so obstruction rules are strict.
- Roof slope: the roof or ceiling above ESFR heads should not slope more than about 10° (2 in 12).
- Not suitable alone: racks with solid shelves, and some high-hazard commodities, still need in-rack sprinklers or another design.
What to tell us
- Building
- Roof height and roof type or slope
- Storage
- Storage height, rack type (open-frame or solid shelves) and commodity
- Obstructions
- Beams, ducts, lights and cable trays at roof level
- Water supply
- Existing pump and tank capacity, if any
- Approval
- UL listed, FM approved or other, as your insurer or consultant requires
ESFR systems need a large water supply, so we check pumps and tanks together with the heads.
Supply, installation and servicing
We supply ESFR heads as part of a designed warehouse sprinkler system, with hydraulic calculations and, where needed, seismic bracing. During AMC visits we check that heads are clear of stored goods and new obstructions, and that storage heights have not grown past the design.

Why choose Cease Fire
Since 1992
A Maharashtra Fire Services Licensed Agency (MFS/
LA/ ) with 1,500+ projects.RF-93/ RD-95 Warehouse experience
Roof sprinklers with seismic bracing for Roquette India's four godowns in Pantnagar, to FM guidelines.
One team
Hydraulic design, sprinklers, fire pumps, installation and AMC.
Request a sprinkler quote
Send your warehouse drawings with roof height, storage height, rack type and commodity. We will review the design and quote.
Frequently asked questions
What is an ESFR sprinkler?
ESFR stands for early suppression, fast response. It is a large-orifice sprinkler that opens quickly and discharges a heavy flow of water to suppress fires in high-piled and rack storage.
Where are ESFR sprinklers used?
Mainly in warehouses and stores with high-piled or rack storage. They are fitted at roof level and can often avoid the need for in-rack sprinklers.
What K-factors are ESFR sprinklers available in?
Common K-factors are K14.0, K16.8, K22.4 and K25.2 (K200, K240, K320 and K360 in metric units). The design sets which one is needed.
Do ESFR sprinklers replace in-rack sprinklers?
Often, but not always. Racks with solid shelves, very high storage and some commodities still need in-rack sprinklers.
Why are obstructions a problem for ESFR sprinklers?
ESFR heads work by getting a heavy spray down to the fire fast. Beams, ducts or lights near the heads can block that spray, so the layout must follow strict obstruction rules.
Can you supply UL listed or FM approved ESFR sprinklers?
Yes. UL listed and FM approved sprinklers are available. Tell us what your consultant or insurer specifies, and we will share the manufacturer's certificate for the exact model with our quote.
Have you installed roof sprinklers for warehouse storage?
Yes. We installed roof sprinklers with seismic bracing for Roquette India's four godowns in Pantnagar, to FM guidelines. See the project page.
Question not answered here? Call our team, Monday to Saturday, 9 am to 7 pm.
Call +91 9920676281