Sprinkler Flow Switch in Mumbai

Cease Fire & Electrical Services LLP supplies, installs and tests the sprinkler flow switch in Mumbai for high-rise towers, offices, hospitals, hotels, warehouses and factories. A sprinkler flow switch senses water moving in the pipe when a sprinkler head opens, and signals the fire alarm or annunciator panel so people know which floor or zone is affected. We fit flow switches at each floor or zone control valve and test them with the panel they report to.
How a vane-type flow switch works
- Vane (paddle)
- A thin flexible paddle sits inside the pipe and is pushed along when water flows
- Switch contacts
- The paddle movement operates switch contacts wired to the fire alarm or annunciator panel
- Adjustable delay (retard)
- The switch waits for a set time before signalling, so a brief pressure surge does not cause a false alarm
- Saddle and gasket
- Clamp the switch to the pipe over a drilled hole and seal it
Listed vane-type switches typically signal at a flow of about 38 litres per minute (10 US gallons per minute). The vane is chosen to suit the pipe size.
Where flow switches are fitted
- On each floor or zone of a sprinkler system, so the panel shows exactly where water is flowing
- Downstream of the sprinkler alarm valve on a wet system riser
- On branch mains serving separate areas, such as basements, podiums and car parks
- Vane-type flow switches are used on wet sprinkler systems. On dry or pre-action systems, a pressure switch on the valve is used instead, because a sudden rush of water can damage a vane.
What to tell us
- Pipe
- Pipe size and schedule where each switch will be fitted
- System
- Wet, dry or pre-action
- Panel
- Fire alarm or annunciator panel it will report to
- Quantity
- Number of floors or zones
- Approval
- UL listed, FM approved or other, as your specification requires
Supply, installation and servicing
We supply flow switches on their own or as part of a zone control valve set with the valve, test and drain valve and pressure gauge. We fit them on the top half of horizontal pipes so debris cannot jam the vane, set the delay, and wire them to the panel. At commissioning and on every AMC visit we open the test and drain valve on each zone and check that the right alarm appears at the panel.

Why choose Cease Fire
Since 1992
A Maharashtra Fire Services Licensed Agency (MFS/
LA/ ) with 1,500+ projects.RF-93/ RD-95 Sprinklers and detection together
We have delivered sprinkler and fire detection packages together, such as Palkhi Roha, Kandivali East (G + 14).
One supplier
Flow switches, valves, modules, panels and installation from one team.
Request a quote
Send your BOQ or drawings with the pipe sizes and number of zones. We will confirm the specification and quote.
Frequently asked questions
What is a sprinkler flow switch?
It is a device that senses water flowing in a sprinkler pipe and sends a signal to the fire alarm or annunciator panel. It shows that a sprinkler head, or the test valve, has opened on that floor or zone.
How does a vane-type flow switch work?
A paddle inside the pipe is pushed by the moving water and operates a switch. A built-in delay stops short pressure surges from raising a false alarm.
What is the difference between a flow switch and a pressure switch?
A flow switch senses water moving past a paddle in the pipe and is used on wet systems. A pressure switch senses the pressure change at an alarm, dry or deluge valve, and is used where a paddle could be damaged.
Why does my sprinkler flow switch give false alarms?
Common causes are pressure surges when the fire pump starts, a delay set too short, or a damaged vane. We check the delay setting and the vane during AMC visits.
How is a sprinkler flow switch tested?
Water is flowed through the zone's test and drain valve, which simulates one sprinkler head opening. The panel should show the alarm for that zone within the set delay.
Can you supply UL listed or FM approved flow switches?
Yes. UL listed and FM approved sprinklers and valves are available. Tell us what your consultant or insurer specifies, and we will share the manufacturer's certificate for the exact model with our quote.
Can you fit flow switches on an existing sprinkler riser?
Yes. We fit the switch on the top half of a horizontal pipe, set the delay, wire it to your panel and test it by flowing water through the zone test valve.
Question not answered here? Call our team, Monday to Saturday, 9 am to 7 pm.
Call +91 9920676281