Water Curtain Nozzle for Drencher Systems in Mumbai

Cease Fire & Electrical Services LLP supplies and fits the water curtain nozzle for drencher systems in Mumbai, protecting openings, building faces, escalator voids and the gaps between buildings or plant areas. A water curtain nozzle is an open nozzle, with no heat-sensitive bulb, that spreads water into a flat sheet to hold back heat and flame. All the nozzles in a zone discharge together when the deluge valve feeding them opens.
How a water curtain nozzle works
Pendent, facing a wall or opening
What it doesWets the wall, window or door so it stays cool
Typical useWindows, glazing, doors and other openings exposed to a fire nearby
Horizontal, spraying downwards
What it doesForms a flat curtain of water from ceiling to floor
Typical useDividing a large space, escalator and stair voids, openings between areas
The nozzles are open, so they do not operate one by one like sprinkler heads. They sit on a dry pipe network behind a deluge valve, which releases water to the whole row when the detection system or a manual release operates it.
Where water curtain nozzles are used
- Openings in fire walls and compartment walls
- Escalator voids and atriums
- Glazing and facades facing another building or a hazard
- Loading bays, stores and plant areas that need to be separated
- Tank farms and process areas, alongside water spray systems
What to tell us
- Application
- Opening, facade, void, tank or other
- Width to cover
- Length of the curtain and height from nozzle to floor
- Design
- Nozzle spacing, flow and pressure from the hydraulic design, if you have one
- Thread and finish
- Inlet size and material, such as brass or stainless steel
- Approval
- UL listed, FM approved or other, as your specification requires
We match the nozzle, spacing and deluge valve to the design before supply. If there is no design yet, our engineers can prepare one.
Supply, installation and servicing
We supply water curtain nozzles on their own or as part of a complete drencher system with the deluge valve, strainer, pipework and detection. At commissioning we flow-test the curtain to check that it is continuous across the full width. During AMC visits we check for blocked or painted nozzles, clean strainers, and test the deluge valve release.

Why choose Cease Fire
Since 1992
A Maharashtra Fire Services Licensed Agency (MFS/
LA/ ) with 1,500+ projects.RF-93/ RD-95 Complete drencher packages
Nozzles, deluge valves, pipework and detection from one team, designed and tested together.
Design support
Nozzle spacing and water demand checked by our engineers with hydraulic calculations.
Request a quote
Send your BOQ or drawings with the curtain length, height and number of nozzles. We will confirm the specification and quote.
Frequently asked questions
What is a water curtain nozzle?
It is an open nozzle that spreads water into a flat sheet or curtain. It has no bulb, so it discharges as soon as water reaches it.
What is the difference between a water curtain nozzle and a sprinkler?
A sprinkler head is closed and opens on its own when its bulb breaks in the heat of a fire. A water curtain nozzle is always open, and every nozzle in the zone discharges together when the deluge valve opens.
Where are water curtain nozzles used?
They protect openings, glazing and facades, escalator voids and other gaps where a fire could spread from one area to another. They are also used around tanks and process areas.
Is a drencher nozzle the same as a water curtain nozzle?
In practice, yes. Both names describe open nozzles used in drencher systems to form a curtain of water.
How is a water curtain system started?
The nozzles are fed by a deluge valve. It opens on a signal from the detection panel, or it can be opened by hand.
Can you supply UL listed or FM approved water curtain nozzles?
Yes. UL listed and FM approved sprinklers and valves are available. Tell us what your consultant or insurer specifies, and we will share the manufacturer's certificate for the exact model with our quote.
Do you design the water curtain layout if we have no drawings?
Yes. Our engineers prepare the nozzle spacing and water demand with hydraulic calculations, then supply the nozzles, deluge valve and pipework as one drencher package.
Question not answered here? Call our team, Monday to Saturday, 9 am to 7 pm.
Call +91 9920676281





