Inert Gas Fire Suppression System in Mumbai

Cease Fire & Electrical Services LLP designs, installs and maintains the inert gas fire suppression system for data centres, large server and control rooms, archives and electrical rooms in Mumbai. An inert gas fire suppression system floods the room with natural gases such as argon and nitrogen, lowering the oxygen level to a point where the fire goes out but people can still breathe for a short time. The gases leave no residue, do not harm the ozone layer and have no global warming potential, which makes them a long-term choice as HFC and PFAS rules tighten.

How an inert gas system works

Smoke detectors in two zones sense a fire and signal the releasing panel. The panel sounds hooters and strobes, counts down so people can leave, and then opens the cylinder bank. The gas flows through pipework, pressure-reducing devices and nozzles into the room. It replaces part of the air and lowers the oxygen level from the normal 21% to a level at which the fire cannot keep burning. At a 43% design concentration, for example, oxygen falls to about 12%, which people can tolerate for a short time.

Types of inert gas

IG-541
A blend of nitrogen, argon and a small amount of CO2
IG-55
50% nitrogen and 50% argon
IG-01
Pure argon
IG-100
Pure nitrogen

We choose the agent from the room, the hazard and the listed systems available for your project.

Inert gas or clean agent?

  1. Agent

    Natural gases from the air

    Man-made chemical agents

  2. Environmental impact

    No global warming potential

    HFC-227ea is being phased down; FK-5-1-12 is affected by PFAS rules

  3. Discharge time

    About 60 seconds to reach design concentration

    About 10 seconds

  4. Storage space

    More cylinders, stored at high pressure

    Fewer, smaller cylinders

  5. Pipe distance

    Gas can travel long distances, so one bank can serve several rooms

    Cylinders usually close to the room

  6. Suits

    Large rooms, several rooms from one bank, long-term projects

    Smaller rooms and tight plant space

Where inert gas systems are used

  • Data centres and large server halls
  • Control rooms and telecom exchanges
  • Archives, museums and record stores
  • Electrical and switchgear rooms
  • Several rooms protected from one central cylinder bank

Safety in occupied rooms

NFPA 2001 limits how long people may be exposed to reduced oxygen. At design concentrations that bring oxygen down to about 12%, exposure of up to 5 minutes is permitted; lower oxygen levels allow shorter exposures, and very low levels are only for unoccupied rooms. We design every system so the oxygen level suits the room's use, with warnings and a countdown before release.

Components

  • Two red gas suppression cylinders strapped to a wall, with valves, gauges and discharge hoses to a manifold

    Cylinder bank with valves

    Stores the inert gas at high pressure

  • A steel pressure-reducing union between two lengths of red pipe

    Pressure-reducing device

    Lowers the pressure so lighter pipework can be used downstream

  • Three selector valves in a row on a red manifold, each with an actuator on top

    Selector valves

    Direct the gas to one of several rooms from a shared bank

  • A red discharge pipe under a ceiling with two metal discharge nozzles

    Discharge pipework and nozzles

    Spread the gas through the room and voids

  • A square grey pressure relief vent with louvre blades set in a concrete wall

    Pressure relief vents

    Let air out of the room during discharge, so walls and doors are not damaged

  • Three white round smoke detectors fixed in a row to a concrete ceiling
  • Two red fire alarm sounders with clear strobe lenses, fixed to a concrete wall

    Hooters, strobes and warning signs

    Warn people to leave before discharge

Design standards

We design inert gas systems to NFPA 2001, the standard for clean agent fire extinguishing systems, which includes inert gases, and to UL/FM requirements where the project calls for them. For every room we prepare a design sheet showing the volume, hazard class, design concentration, gas quantity, cylinders, nozzles and the pressure relief vent size. The room must hold the gas for at least 10 minutes, so we check openings and can arrange a door fan test.

Our process

  1. Free site survey

    We measure the rooms and voids, check wall and door strength, openings, and space for the cylinder bank.

  2. Design

    Gas quantity calculation, cylinder bank, pipework, nozzles, pressure relief vents, detection and release sequence.

  3. Supply and installation

    Cylinders, pipework, nozzles, vents, detectors and the releasing panel, installed by our own team.

  4. Testing and commissioning

    Detection and release circuits tested, room openings sealed, and staff trained on the warning and abort sequence.

  5. Form A

    As a licensed agency, we issue Form A for the work, which you submit to the fire brigade.

  6. AMC and Form B

    Cylinder pressure checked at least every six months, and Form B every January and July.

Our experience

  • Licences

    Maharashtra Fire Services Licensed Agency (MFS/LA/RF-93/RD-95) and Maharashtra Electrical Contractor Licence No. 17545.

  • Electrical and utility work

    Addressable fire alarm systems at 65 Adani Electricity receiving substations across Mumbai, May 2024 to January 2026.

  • Clients

    Including TCS, BPCL, Godrej and Adani Electricity Mumbai.

See all projects and case studies

Maintenance and Form B

Under AMC we check the pressure of every cylinder at least every six months, test the detectors, panel, actuators, selector valves and warning devices each year, and check that the pressure relief vents and room openings are unchanged. A licensed agency must inspect the fire systems and issue Form B every January and July, and we can include this in your AMC.

Why choose Cease Fire

  • Since 1992

    1,500+ projects and the Rashtriya Nirman Ratna Award for Best Government Contractor (2002).

  • Honest agent advice

    Inert gas, FK-5-1-12, FM-200 or CO2, whichever suits the room and your plans.

  • Room-by-room calculations

    A design sheet for every protected room, including vent sizing.

  • Licensed

    We issue Form A and Form B ourselves.

Book a free site survey

Send us the room sizes, including any false ceiling and raised floor, and where a cylinder bank could go. We will send a proposal with a design sheet for each room.

Frequently asked questions

What is an inert gas fire suppression system?

It is a system that floods a room with natural gases such as argon and nitrogen. The gases lower the oxygen level enough to put out the fire, without residue or water damage.

Is inert gas safe for people?

At normal design concentrations, people can tolerate the reduced oxygen for a short time. NFPA 2001 allows up to 5 minutes' exposure when oxygen is reduced to about 12%, but people should still leave when the alarm sounds.

What are IG-541, IG-55, IG-01 and IG-100?

They are the main inert gas agents. IG-541 is nitrogen, argon and a little CO2; IG-55 is half nitrogen and half argon; IG-01 is argon; and IG-100 is nitrogen.

Why does an inert gas room need a pressure relief vent?

A large volume of gas enters the room during discharge. The vent lets air out so the pressure does not damage walls, doors or ceilings.

Is inert gas better than FM-200?

Inert gas has no global warming potential and suits large rooms and several rooms from one bank. It needs more cylinder space and discharges more slowly, so the right choice depends on the room.

Can one inert gas system protect several rooms?

Yes. A shared cylinder bank with selector valves can protect several rooms, because the gas can travel long distances through pipework.

How often should an inert gas system be checked?

Cylinder pressure should be checked at least every six months, with a full inspection each year. A licensed agency must also inspect the fire systems for Form B every January and July.

How long does an inert gas discharge take?

Inert gas systems take about 60 seconds to reach the design concentration, compared with about 10 seconds for halocarbon clean agents. The warning and countdown are set to match.

Question not answered here? Call our team, Monday to Saturday, 9 am to 7 pm.